CHAPTER
5 - FOUNDATION REQUIREMENTS
500. GENERAL. This
section outlines general material and quality standards for all foundations in
this manual.
501. EXCAVATION
501-1. FOOTING
DEPTH. Excavation for footings or foundation walls shall extend
below depth of soil subjected to seasonal or character-istic volume change to
undisturbed soil that provides adequate bearing. Select the greatest depth
required by any of the provisions below, reference Figure 5-1.
A. Maximum Frost
Penetration Depth. The bottom of footings shall extend at least
to the depth indicated on the map on page H-4.
B. Alternate
Seasonal Wetting and Drying. This is especially important with ex-pansive
soils. If expansive soils exist, consult a geotechnical engineer to obtain
required foot-ing depth.
C. Footing Depth. The
footings shall be deep enough to provide required uplift capac-ity. (This value
may need to be determined for high wind areas after the calculations needed to
determine footing bearing have been com-pleted.)
502. FOUNDATION
MATERIALS. Footings and foundations shall be constructed of solid
materials such as masonry, concrete, or treated wood, based on the Foundation
Design Concept Selection (Appendix A) and Founda-tion Capacity Tables.
(Appendix C) (For ma-sonry and concrete refer to CABO R-302.2, R-304.1 and
R-304.3; for wood refer to CABO R-302.1 and R-304.5.)
503. STRUCTURAL
REQUIRE-MENTS
503-1. FOUNDATION
REQUIREMENTS. All exterior walls, marriage walls, marriage wall posts,
columns and piers, must be sup-ported on an acceptable foundation system that
must be of sufficient design to support safely the loads imposed, as determined
from the character of the soil.
A. Height Above
Grade. Foundation walls shall extend at least 8" above the
finished grade adjacent to the foundation at all points. See Figure 5-1.
B. Minimum
Foundation Wall and Wall Footing Thickness. For masonry or concrete
construction, the minimum foundation wall will be 6 inches. The minimum
reinforced concrete footing thickness will be 6 inches or 1-1/2 times the
length of the footing projection from the foundation wall, whichever is
greater.
503-2. PIER AND
COLUMN FOOTING REQUIREMENTS. Footings for pier founda-tions shall be
reinforced concrete and should be placed level on firm undisturbed soil of
ade-quate bearing capacity and below the frost penetration depth. They can also
be placed on engineered, compacted fill, approved by a li-censed geotechnical
engineer.
A. Unusual
Conditions. Where unusual conditions exist, the spacing of piers and
pier size and the load bearing capacity of the soil shall be determined
specifically for such condi-tions.
B. Minimum Pier and
Pier Footing Thickness. The minimum thickness for a pier is 8 inches.
The minimum thickness for pier footings is 8 inches or 1-1/2 times the length
of the footing projection from the pier, whichever is greater.
503-3. FOOTING
REINFORCING (HORIZONTAL). Reinforce footings when the projection on
each side of the wall, pier, or column exceeds 2/3 of the footing thickness, or
when required because of soil conditions.
503-4. MASONRY
PIERS AND WALLS. All masonry piers and walls shall have
mor-tared bed and head joints. Reinforcing and grouting shall be in accordance
with the foun-dation concept selected from Appendix A and designed in Appendix
C.
503-5. CRAWL SPACE
REQUIRE-MENTS (Basementless spaces)

Minimum Clearances and Footing Depth
Figure 5 - 1
A. Height Requirement. Ground level must be
at least 18 inches below bottom of wood floor joists and 12 inches below bottom
of chassis beam. Where it is necessary to pro-vide access for maintenance and
repair of me-chanical equipment located in the under floor space, the ground
level in the affected area shall not be less than 2 feet below wood floor
joists. (Refer to CABO, Section R-309.) See Figure 5-1.
B. Interior vs. Exterior Ground Level. The
interior ground level must be above the outside finish grade unless:
1. Adequate gravity drainage to a posi-tive
out fall is provided, or
2. The permeability of the soil and the
location of the water table is such that water will not collect in the crawl
space, or
3. Drain tile and automatic sump pump system
are provided.
C. Openings. Locations of crawl space
openings and ventilation openings should be on long foundation walls. Avoid any
openings on short foundation walls. Sill plates or other structural members
should not be randomly cut to accommodate openings. Continuity of struc-tural
members must be maintained.
503-6. FOUNDATION WALLS FOR BASEMENTS. The
design and reinforcing of basement walls is NOT in the scope of this document.
Refer to local codes and ordinances for guidance. Refer also to CABO, Section
R-304: "Foundation Walls." Design the unit’s foundation based on soil
conditions present at the site.
503-7. BACK FILL. Material used for back fill
must be clean and free of wood scraps or other deleterious substances and must
be placed carefully against walls.
503-8. STEEL BEAMS AND COLUMNS. The analysis
and design of steel transverse girders, steel longitudinal girders potentially
used under marriage walls to reduce the num-ber of steel pipe columns within a
basement, and the steel pipe columns themselves are NOT within the scope of this
document for system Types E5, E6 and E7